EMT 6000 Series
60W AC/DC Converter
|
|
 |
Compact (100x100x43mm)
|
 |
Wide Input Range |
 |
12, 24, 48V |
 |
Parallel able |
 |
Easy Mounting |
 |
Solid ALU Housing |
|
|
|
SPECIFICATIONS |
|
GENERAL |
|
| INPUT VOLTAGE |
85 -
265 VAC |
|
P/S CAPACITY |
< 1,2 nF
PRIM/SEC |
| 120 -
375 VDC |
ISOLATION |
PRIM/SEC
3750 V |
| INPUT
POWER |
<
110VA |
CREEPAGE |
8 mm |
| FILTER |
HIGH EFFICIENCY COMMON MODE |
EMC |
EN55022
- VDE 0871 |
| SAFETY |
IEC
950, EN 60950 |
| FUSE |
T 2,0
A |
PREFUSING
|
MAX 30 A |
| INRUSH |
<
20 A |
DERATING |
0
- 50° C NONE |
| INPUT
FREQ. |
45 -
65 Hz |
MTBF |
> 450.000 Hours |
| PROTECTION |
275
VAC VARISTOR |
OUTLINE |
100 x100 x 43
mm |
| EFFICIENCY |
79 - 86
% |
WEIGHT |
APPR.
370 g |
| FREQUENCY |
Appr.
70 Khz |
OPERATING |
0 - 55
° C See FIG. 2 |
| HOLD-UP TIME |
>
20 mSec. |
STORAGE |
-40 - +85 ° C |
OUTPUT |
|
| TYPE: |
EMT
6012 |
EMT
6024 |
EMT
6048 |
| VOLTAGE |
+12 VDC |
+24
VDC |
+48 VDC |
| POWER |
50 W MAX |
60
W MAX |
60 W MAX |
| CURRENT LIMIT |
5,0 A See Curve
FIG.3 |
2,6
A See Curve FIG.3 |
1,3 A See Curve
FIG.3 |
| ADJUST RANGE |
11,8 - 13,8 VDC |
23,5
- 27,6 VDC |
47,0 - 55,2 VDC |
| RIPPLE |
< 1,0 % |
< 0,8 % |
< 0,8 % |
| LOAD REG. |
< 1,5 % |
< 1,0 % |
< 0,8 % |
| LINE REG. |
< 0,1 % |
< 0,1 % |
< 0,1 % |
| PARALLEL OPR. |
80 % POWER SHARE |
90 % POWER SHARE |
90 % POWER SHARE |
| FACTORY ADJUST |
12,10 VDC +/-0,01V
@ 0 A |
24,10 VDC +/-0,01V
@ 0 A |
48,10 VDC
+/-0,01V @ 0 A |
|
|
|
|
| Battery Charging: |
By
charging Lead Acid Batteries, adjust unit to shown charge voltage with no load
connected.
This will keep your Battery charged to 90 - 96% under normal temp.
conditions, in normal
standby operation.Or contact your local Battery Supplier,
for technical information around Charge Voltage in Standby Operation and readjust unit to
desired voltage, with no Load. |
CHARGE
VOLTAGES |
| Batt |
Volts |
| 12V |
13,8 V |
| 24V |
27,6 V |
| 48V |
55,2V |
|
|
| Parallel Operation: |
|
|
|
|
| When
connecting in parallel, use the same wire diameter/length from unit to common tie point,
to best parallel performance. Units are factory adjusted, to
above voltages, to obtain best performance in parallel operation, - - if this adjustment
is changed, readjust unit's to wanted Output voltage (+/- 10mV) with no Load for each
unit, before connecting in parallel. |
|
 |
Current Limit:
Looking at Fig. 3 a typical Current Limit is shown
together with Toggle Mode point.
This point is at 40 - 60 % of rated Output Voltage on all units.When unit reaches its Toggle Mode point, unit will stop, and with its
automatically restart within seconds, unit will in this mode stand a constant short with no
damage or internal power losses. |
| |
|
 |
 |
| |
|
Dimensions:
|
|

|
|
|